Check out this video. You would put one or more Normally Closed momentary buttons to in series with the red button, along with as many Estop switches as you want. The beauty of this is that only the coil control voltage has to run to the switches. Your loads would be run through the main input/output terminals of the contactor. Probably the positive leg of each power circuit. Hopefully this makes sense.